Plate Heat Exchangers as a Compact Design and Optimization of Different Channel Angles

Authors

Content

Title variants

Languages of publication

EN

Abstracts

EN
In this study, thermal treatments have been investigated for different channel angles and mass flow rates of a compact heat exchanger have been manufactured by direct metal laser sintering technique instead of a sealed and brazed one used in many areas. Boundary conditions of available heat exchanger experimental test have been used in laboratory. In this study, we have designed for compact heat exchanger of 30°, 45° and 60° channel angle and used three different mass flow rates (0.2, 0.3, and 0.43 kg/s). Heat transfers occurring between heat channels and walls of heat exchangers for different channel angles and efficiency of heat exchangers have been calculated. As a result of the analysis, it has been determined that in order for maximum of heat transfer of a compact heat exchanger, following working conditions ought to be fulfilled: channel angle 30°, hot water input temperature 60°C, cold water input temperature 15°C, and mass flow rate 0.43 kg/s.

Keywords

EN

Year

Volume

128

Issue

2B

Pages

B-49-B-52

Physical description

Dates

published
2015-8

Contributors

author
  • Mechanical Engineering, Isparta, Turkey
author
  • Mechanical Engineering, Isparta, Turkey
author
  • Mechanical Engineering, Isparta, Turkey

References

  • [1] M. Reppich, J. Kohoutek, Chem. Eng. Proc. 18, 295 (1994), doi: 10.1016/0098-1354(94)80049-9
  • [2] N. Hopkinson, P. Dickens, J. Eng. Manufact. 214, 891 (2000), doi: 10.1243/0954405001517973
  • [3] J.A.W. Gut, J.M. Pinto, Int. J. Heat Mass Transf. 47, 4833 (2004), doi: 10.1016/j.ijheatmasstransfer.2004.06.002
  • [4] A. Franco, N. Giannini, Appl. Therm. Eng. 25, 1293 (2004), doi: 10.1016/j.applthermaleng.2004.08.018
  • [5] A. Erek, B. Özerdem, L. Bilir, Z. İlken,Appl. Therm. Eng. 25, 2421 (2005), doi: 10.1016/j.applthermaleng.2004.12.019
  • [6] A. Durmus, H. Benli, I. Kurtbas, H. Gul,Int. J. Heat Mass Transf. 52, 1451 (2009), doi: 10.1016/j.ijheatmasstransfer.2008.07.052
  • [7] D. Dovic, B. Palm, S. Svaic, Int. J. Heat Mass Transf. 52, 4553 (2009), doi: 10.1016/j.ijheatmasstransfer.2009.03.074
  • [8] O. Yildirim, Z. Guo, 'High-efficiency Micro Channel Regenerative Heat Exchanger for Fluid Processing', in: Comsol User Conf., 2011. http://comsol.com/papers/10786
  • [9] I. Gherasim, M. Taws, N. Galanis, C.T. Nguyen,Int. J. Therm. Sci. 50, 1492 (2011), doi: 10.1016/j.ijthermalsci.2011.03.018
  • [10] S. Mancin, D.D. Col, L. Rossetto, Exp. Therm. Fluid Sci. 36, 149 (2012), doi: 10.1016/j.expthermflusci.2011.09.007
  • [11] M. Faizal, M.R. Ahmed, Exp. Therm. Fluid Sci. 36, 242 (2012), doi: 10.1016/j.expthermflusci.2011.09.019
  • [12] B. Kılıç, Ph.D. Thesis, Suleyman Demirel University Natural and Science Institution, Isparta 2013, p. 50
  • [13] Fluent, Version 14.0 User's Guide, Fluent Inc., Lebanon (NH) 2013
  • [14] W.M. Kays, A.L. London, E.R.G. Eckert, Compact Heat Exchangers, Krieger Publ. Co., Malabar, Florida 1960, doi: 10.1115/1.3644004